The Tyco PSU830 (557.202.210) is an integrated power supply and battery charger module for Tyco MX/MZX fire detection systems. It combines switch-mode power conversion, battery charging, fault monitoring, and a loop booster to provide reliable power for addressable fire detection equipment.
Features
- Integrated switch-mode power supply and battery charger.
- Universal 100–264 VAC input supports different mains supplies.
- Provides up to 5 A during alarm conditions.
- Temperature-compensated battery charging.
- Built-in loop booster for optimized MX Digital protocol performance.
- Can support up to four fully loaded MX digital loops.
- Provides monitoring for AC loss, battery fault, charger fault, and earth fault.
- Battery voltage monitoring is provided to the FIM/APM800.
- Provides separate 27 VDC, 40 VDC and 5 VDC outputs for system equipment and accessories.
- Designed for compatibility with Tyco MX/MZX fire detection systems.
- Meets EN 54-4 requirements for power supply equipment.
Typical Applications
- Marine fire detection and alarm systems
- Tyco MX/MZX addressable fire panels
- Shipboard fire alarm control panels
- Engine-room fire detection systems
- Offshore fire and safety systems
- Addressable fire detection loop power supply
- Battery-backed emergency fire alarm systems
- Replacement and retrofit of compatible Tyco power supplies