The Autronica BD-26/EX is a conventional fixed-temperature heat detector designed for damp and hazardous areas. It provides an alarm at 56°C under slow temperature rise, while a rapid temperature increase can cause alarm at a lower temperature. It is certified for Zone 1 and Zone 2 hazardous areas and uses thermistor-based temperature measurement.
Key Features
- Fixed-temperature heat detection with a 56°C alarm threshold under slow heating.
- Rapid temperature rise can initiate an alarm at a lower temperature.
- IP56 construction, making it suitable for damp and demanding environments.
- EExib explosion-protected version for hazardous Zone 1 and Zone 2 applications.
- Requires connection through the Autronica BZ-20 zener barrier for the specified hazardous-area installation.
- Built-in alarm LED indicator.
- Can be incorporated into an analogue addressable system using an appropriate interface unit.
- Particularly useful where smoke detectors could produce unwanted alarms.
Typical Applications
- Shipboard and marine fire detection systems
- Offshore platforms and installations
- Oil & gas hazardous areas
- Industrial/process areas
- Damp or humid locations
- Areas where smoke detectors are unsuitable because of false-alarm risk