The Autronica BSD-340/2 is a PowerLoop Driver used in the AutroSafe fire and gas detection system. It functions as a protocol converter between AutroFieldBus and PowerLoop, providing both power and communication to detectors and other loop units.
Features
- Functions as a protocol converter between AutroFieldBus and PowerLoop.
- Provides both power and communication to PowerLoop devices.
- Supports a 30 VDC / 100 W PowerLoop.
- PowerLoop is galvanically isolated from the rest of the system.
- Supports up to 15 detectors per PowerLoop, subject to system calculations.
- Provides a D-sub 9-pin service port for commissioning and maintenance.
- AutroFieldBus address can be set using switches.
- DIN-rail mounted design for convenient panel installation.
- Monitors and reports earth faults, open/short circuits, missing loop units, output-voltage faults and internal faults.
- Designed for demanding marine and industrial fire & gas detection systems.
Typical Applications
- AutroSafe fire and gas detection systems
- Marine vessels and ships
- Offshore platforms
- Oil & gas installations
- Petrochemical facilities
- Industrial fire and gas detection systems
- Systems requiring PowerLoop-connected detectors and field devices
- Expansion, maintenance and replacement of existing AutroSafe installations.