The Autronica BZ-32/1 is a Zener barrier unit used with Autronica addressable fire detection systems to interface fire detectors installed in hazardous areas. The /1 designation means the unit contains one Z-667/Ex Zener barrier and supports one detector branch.
Key Features
- Intrinsic-safety interface between the safe-area fire alarm system and hazardous-area detector circuits.
- Incorporates one Z-667/Ex Zener barrier.
- Provides one hazardous-area detector branch for the BZ-32/1 version.
- Each branch can accommodate up to 10 addresses, subject to the system configuration.
- Designed for use with the Autronica BS-100 analogue addressable fire alarm system.
- Helps limit electrical energy entering the hazardous area, providing intrinsic-safety protection.
- The enclosure is specified with IP55 encapsulation/protection.
- Safe-area and hazardous-area cabling must be kept separated; the documentation specifies a minimum 50 mm separation inside and outside the housing.
Typical Applications
- Marine fire detection systems
- Offshore platforms and installations
- Hazardous-area fire detection
- Engine rooms and machinery spaces
- Oil & gas installations
- Petrochemical and industrial hazardous areas
- Connection of Ex-approved smoke, heat and manual call-point detectors to an Autronica BS-100 system